S.C.F.D. School Inspections

Slide 2

Priorities Life Safety Records Corridors Boiler rooms Kitchens Exit doors Fire doors

Slide 3

Fire Drill Documentation Posted Monthly drills, 1 per calendar month during school months. Should be one for August, Sept, Oct, so on and so forth.

Slide 4

Fire Drill Map Should be one in each room Don’t check every room Check a few

Slide 5

Fire Drill Procedures for disabled Ask for copy of procedures. Don’t have one? Violation..

Slide 6

Tornado drill documentation on State record form Ask to see the record Should be on State provided form.

Slide 7

Tornado refuge Information sheet Conspicuously posted Near main entrance Lobby area Hallway area

Slide 8

Fire Alarm Serviced? Must be within last 12 months Must be monitored off-site You must see proof Is there a power on light? Is there a trouble light? Trouble light, require service within 1 week. No power light, immediately call fire prevention!

Slide 9

Sprinkler system service? If they have one Within last 12 months State certified contractor Not the alarm company

Slide 10

Boiler Certification If they have them Within last 18 months Will be an actual certificate

Slide 11

Kitchen hood extinguishing system Serviced within last 6 months You must see proof Remove old links that have been taken out of the system & dispose of them.

Slide 12

Emergency lighting test record Have they been testing monthly Must be documented You must see the record Regular lighting may be on generator If so, are they testing generator regularly, should have generator test record?

Slide 13

Emergency lighting operation Spot check at least 10 of them Any of them not work? Do a lot of them not work? If so check them all and get a count.

Slide 14

Exit Signs Are they all working? Spot check backup battery on at least 10 of them. Do they all work? Are they obstructed?

Slide 15

Exit Doors Do they all open easily? Are they blocked? Any hardware locks that don’t belong?

Slide 16

Fire Doors Magnetic doors close easily and properly? Are they blocked open?

Slide 17

Corridor width 6 foot minimum Desks, chairs, shelves in the way? No coats or clothing in halls, even on hangars.

Slide 18

Fire Extinguishers In place? Serviced?

Slide 19

Flammable contents and decorations Straw, Hay? Cardboard storage? Decorations

Slide 20

Corridor displays 20% of the corridor is the rule Judgment call, is there too much?

Slide 21

Unvented heating No unvented heating equipment Remove immediately

Slide 22

LPG Cylinders For classroom use I.E. Shop areas etc. No bigger than 20 lb.

Slide 23

Other normal inspection items That you do on any business Electrical issues Furnace rooms Combustible storage Blocked breaker box Water cooler fountains should be on GFI circuit. etc